Home » Product List » DIN-RAIL MOUNT PSU » 60W DIN Rail Switching Power Supply (DR-60)
Product Details
60W DIN Rail Switching Power Supply (DR-60)
| Packing: | Export Packing |
|---|---|
| Model NO.: | DR |
| Standard: | 60 |
| Productivity: | 5000PCS/Month |
| Trademark: | Sino-Amigo |
| Origin: | China |
| Output Type: | Single |
| Output Power: | 51 - 100W |
| Input Voltage: | Full Range |
| Export Markets: | North America, South America, Eastern Europe, Southeast Asia, Africa, Oceania, Mid East, Eastern Asia, Western Europe |
Product Description
High Efficiency, High Reliability, Low Cost
AC Input Range: 90~264Vac
100% Full Load Burn-In Test
Protections: Short Circuit / Over Load/Over Voltage
LED Indicator For Power On
Cooling By Free Air Convection
Approvals: CE RoHS
1 Year Warranty
| Model | DR-60-5 | DR-60-12 | DR-60-15 | DR-60-24 |
| DC output voltage | 5V | 12V | 15V | 24V |
| Output voltage range | ±2% | ±1% | ±1% | ±1% |
| Rated output current | 6.5A |
4.5A |
4A |
2.5A |
| Output current range | 0-6.5A | 0-4.5A | 0-4A | 0-2.5A |
| Wave and noise | 100mVp-p | 200mVp-p | 240mVp-p | 480mVp-p |
| Inlet stability | ±1% | ±1% | ±1% | ±1% |
| Load stability | ±1% | ±1% | ±1% | ±1% |
| DC output power | 32.5W | 54W | 60W | 60W |
| Efficiency | 72% | 77% | 77% | 80% |
| Adjustable range for DC voltage | 4.75~5.5V | 10.8~13.2V | 13.5~16.5V | 21.6~26.4V |
| AC input voltage range | 85~264VAC 47~63Hz;120~370VDC | |||
| Input current | 1.5A/115V 0.75A/230V | |||
| AC inrush curren | Cold-start current 30A/115V 60A/230V | |||
| Leakage current | <1mA/240VAC | |||
| Overload protection | 105%~150% Type: pulsing hiccup shutdown Reset: tuto recovery | |||
| Temperature coefficient | ±0.03%/°c(0~50°c) | |||
| Setup, rise , hold up time | 800ms, 60ms, 50ms | |||
| Vibration | 10~500Hz, 2G 10min,/1cycle, Period for 60min, Each axes | |||
| Withstand voltage | Input and output internal: Input and encolsur: 1.5KvAC, Output and enclosure: 0.5KvAC | |||
| Isolation resistance | Input and output internal: Input and enclosure, Output and enclosure:500VDC/100MΩ | |||
| Working temperature and humidity | -10°c~+60°c(Refer to output derating curve), 20%~90%RH | |||
| Overall dimension | 78×93×56mm | |||
| Weight | 0.3Kgs | |||
| Safety standards | Meet UL 1012 requiement (Not apply for the mark) | |||
| EMC standards | Meet FCC PART 15 J Conduction class B | |||
|
Note: 1. The testing condition for the paramenter above is: 230VAC input, rated load, 25°c 70% RH. Temperatuer. 2. Error: include the setting error, line stability and load stability. 3. Wave test: adopting "A12" double wire for 20MHz, and 0.1UF&47UF capacitor short-circuit for interrupting. 4. Inlet voltage stability test: when is over load, the lowest voltage of inlet is up to the highest voltage. 5. Load stability test: The load is from 0% to 100%. |
||||